Interruptor de vácuo TD325J
Informação básica
Modelo: VITD 2/1250-25J
Descrição do produto
Interruptor de vácuo
VITD 2/1250-25J
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS | |
1.Rated Frequency | 50/60Hz |
2.Rated Maximum Line to Line Voltage | 12kV,r.m.s |
3.Rated Power Frequency Withstand Voltage:Air | 42kV,r.m.s |
4.Rated Impulse Withstand Voltage:Air | 95kV,Peak |
5.Rated Normal Current | 1250A |
6.Rated Short-Circuit Current(3Phase Symmetrical Basis) | 25kA,r.m.s |
7.Percentage D.C. Component of Rated S.C. Breaking Current | 50% |
8.Rated Short-Circuit Making Current | 63kA,Peak |
9.Rated Duration of Short Time Current | 4s |
10.Rated Short-Time Withstand Current | 25kA,r.m.s |
11.Rated Peak Withstand Current | 63kA,r.m.s |
12.*Maximum Contact Resistance at Minimum Closing Force | 19Micro ohms |
13.*Rated Breaking Current of Single Capacitor Bank | 630A,r.m.s |
14.*Rated Breaking Current of Back-to-Back Capacitor Bank | 400A,r.m.s |
15.Rated operating sequence | o-0.3s-co-180s-co |
MECHANICAL DATA | |
1.Interrupter Weight(Approx.) | 2.01kg |
2.Moving Part Weight(Approx.) | 0.77kg |
3.Closing Force due to Bellow and Atmospheric | 8040N |
4.Force Required to Hold Contacts open at Full Stroke | 12050N |
MECHANICAL REQUIREMENTS(REF. VCB) | |
1.Contact Stroke | 81 mm |
2.Opening Speed(average of 75 contact gap) | 1.10.2m/Sec |
3.Maximum Overtravel During Opening | 2mm |
4.Maximun Rebound During Opening | 2mm |
5.Closing Speed(average of last 30% contact gap) | 0.60.2m/Sec |
6.Maximum Contact Bounse Duration(with maximum 2 bounces) | 2ms |
7.Rated Contact Compressive Force | 2500200N |
8.Closing and Opening non-simultaneity of three-phase Contacts | 2ms |
LIFE (ESTIMATED) | |
1.Electrical Life at Rated Normal Current | 50,000Operations |
2.Electrical Life at Rated Short Circuit Current | 100Operations |
3.Mechanical Life | 50,000Operations |
4.Contact Erosion Limit | 3mm |
5.Shelf Life | 20Years |
1.Meets or exceeds the electrical endurance requirements of class E2 for autoreclosing duty per IEC 62271-200 and JB 8738-2008. 2.* Rated Characteristics to be given on request |
Grupo de Produto : Interruptor de vácuo
Premium Related Products
outros produtos
produtos quentes
Interruptor de vácuo TD324PInterruptor de vácuo TD324YInterruptor de vácuo TD325JInterruptor de vácuo TD325KInterruptor de vácuo TD325YInterruptor de vácuo TD326EInterruptor de vácuo TD326YInterruptor de vácuo TD336GInterruptor de vácuo TD336YInterruptor de vácuo TD358YInterruptor de vácuo TD368YInterruptor de vácuo TD424BInterruptor de vácuo TD425YInterruptor de vácuo TD445ZInterruptor de vácuo TD524AInterruptor de vácuo TD544H